QUICKTRONIC QTI2X35/49/80 DA Quick Overview Product family benefits
System+ Guarantee available Easy integration in luminaire thanks to same dimensions like DALI GI ECG TouchDIM function for easy and inexpensive dimming of several ECGs Same luminous flux with direct and alternating current Dimming of amalgam lamps without flickering or reduced lifespan Automatic restart after lamp replacement DALI product features
Control via the DALI interface Compliance with the DALI Version-1 and IEC 60929 Control input protected against overvoltage and polarity reversal (OSRAM ECG) Touch DIM and Touch DIM Sensor function
Manual dimming without controller and with standard switches Including memory function (double click) and soft start
TECHNICAL DATA Input voltage AC 198…264 V Nominal voltage 220…240 V Mains frequency 50…60 Hz Input voltage DC 154…276 V Operating frequency 44…120 kHz Max. ECG no. on circuit breaker 10 A (B) 5
Max. ECG no. on circuit breaker 16 A (B) 9
Power loss in stand-by mode 0.2 W Inrush current 60 A
Â
LIGHT TECHNICAL DATA
Length 423.0 mm Width 30.0 mm Height 21.0 mm Mounting hole spacing, length 415.0 mm Product weight 370.00 g Wire preparation length, input side 8.0…9.0 mm
Wire preparation length, output side 8.0…9.0 mm
Cable cross-section, output side 0.5…1.5 / 0.5…1.0 mm²
Cable cross-section, input side 0.5…1.5 / 0.5…1.0 mm²
Â
TEMPERATURES & OPERATING CONDITIONS
Ambient temperature range +10…+50 °C Permitted rel. humidity during operation 5…85 %
Â
LIFESPAN
Dimming interface DALI / Touch DIM / Touch DIM Sensor Dimming range 1…100 %
Dimmable Yes Overload protection Yes Overheating protection Power reduction and switch off at T > 75 °C at the tc point Suitable for fixtures with prot. class I End of lamp life safety shutdown EOL T.2
Â
CERTIFICATES & STANDARDS
Approval marks – approval VDE / VDE-EMC / EL / EAC / RCM / CCC Standards Acc. to EN 61347-2-3/Acc. to EN 60929/Acc. to EN 55015:2006 + A1:2007/Acc. to EN 61000-3-2/Acc. to EN 61547/Acc. to IEC 62386-101:Ed1/Acc. to IEC 62386-102:Ed1 EEI – Energy Label A1 BAT Protection class I Type of protection IP20